E30 MK2Digital Pressure Controller

Four pressure switches in one. The E30 MK2 digital pressure switch can be configured to operate as a loss-of-prime switch, pressure guard for high/low protection, single-point snap-action switch, or dual-pump controller — 16 unique functions across 4 operating modes.

E30 MK2

Features

  • Very simple to program
  • Multi-voltage operation
  • Displays pressure and set points
  • Displays running time
  • Powerful 40 A solid-state drive
  • Dedicated 16 A alarm relay
  • Detachable electrical housing
  • 20 bar (290 psi) pressure rating
  • Wall mounting kit included
  • Accepts 2 remote inputs
  • Weatherproof housing

The E30 MK2 Digital Pressure Switch is available in thermoplastic and DR brass construction with a 1/4" BSPF process connection. The standard model operates from 220–240 V AC or from 24 V AC/DC; a dedicated 12 V DC model is also available.

Select Model

Ordering — Available Models

Model NumberDescription
E30-MK2Standard model — 220–240 V AC or 24 V AC / 24 V DC operation
E30-MK2-12Low-voltage model — 12 V DC operation only

Operating Limitations

Ambient temperature range1 °C to 50 °C
Liquid temperature range1 °C to 60 °C
Ingress protection ratingIP64
Maximum operating pressure (static or dynamic)20 bar / 290 psi
Minimum burst pressure (all models)> 30 bar / 435 psi
Trip pressure range0–2000 kPa or 0–290 psi in 1 kPa / 1 psi steps
Snap pressure range (Mode 3 only)1–2000 kPa or 1–290 psi in 1 kPa / 1 psi steps
Snap pressure differential (Mode 3 only)7–140 kPa or 1–20 psi in 7 kPa / 1 psi steps
Starting pressure range0–2000 kPa or 0–290 psi in 1 kPa / 1 psi steps
Stopping pressure range0–2000 kPa or 0–290 psi in 1 kPa / 1 psi steps
Minimum pressure differential (Modes 1 & 2 only)1 kPa or 1 psi (practical limit ≈ 7 kPa / 1 psi)

Electrical Data

Supply voltage (standard model)220–250 V AC or 18–25 V AC/DC (multi-voltage input)
Supply voltage (12 V DC model)11–14 V DC
Maximum motor load (all models)Single-phase motors up to 2.4 kW max at 240 V AC (P1). 3-phase motors of all sizes via a suitable interposing contactor — no maximum motor size applies.
Relay 1 contact rating16 A at 240 V AC resistive
Relay 2 contact rating16 A at 240 V AC resistive

Functions

# = user-settable

#Selectable pressure units (kPa or psi)—
#Start-up timerFully adjustable and self-terminating. 1 second to 4 minutes in 1-second increments.
#Run-on timerFully adjustable and self-terminating. 1 second to 15 minutes in 1-second increments.
#Delayed re-starting timerOnce stopped, delays the restart. 1 minute to 99 hours 59 minutes in 1-minute increments.
#Batch controlSet a specific run time for the pump. 1 minute to 99 hours 59 minutes in 1-minute increments.
#Auto restart if run drySingle or multiple attempts. 1 minute to 99 hours 59 minutes in 1-minute increments.
#Trip pressureFully adjustable and can be turned on or off. 0–2000 kPa / 0–290 psi in 1 kPa or 1 psi steps.
#Snap pressureSet a single switch point. Mode 3 only. 1–2000 kPa / 1–290 psi in 1 kPa or 1 psi steps.
#Snap pressure switching differential (delta)Mode 3 only. 7–140 kPa / 1–20 psi in 7 kPa or 1 psi steps.
#Starting pressureFully adjustable and can be turned off. 0–2000 kPa / 0–290 psi in 1 kPa or 1 psi steps.
#Stopping pressureFully adjustable and can be turned off. 0–2000 kPa / 0–290 psi in 1 kPa or 1 psi steps.
#Anti-cyclingControls the number of motor starts per hour. 1 to 1800 starts/hour.
#Anti-cycling sensitivityAvoids nuisance tripping. Adjustable 2 to 50 sequential starts.
#Output relay select (R1 or R2)User can configure the E30’s output to be relay 1 or relay 2.
#Output relay action (NO or NC)User can configure the E30’s output relay to be normally-open or normally-closed.
#Alarm relay condition (7 selectable)Alarm relay can be set to close on 7 selectable normal or fault conditions.
Pressure / set-point displayDisplays system pressure, high & low pressure set points, and snap pressure point in preferred units.
Fault diagnostic displayDisplays the reasons for faults and alarms on its LCD screen.
Over-pressure alarmAutomatically invoked at 22 bar (319 psi).
Remote start/stopStart and stop a pump using an external low-voltage switch.

Dimensions

E30 MK2 dimensions
Front view, mounting-bracket drill pattern, side view (without and with mounting bracket). 1/4" BSPP female process connection; three M20 cable glands; removable protective cap.

4 Operating Modes

The E30 MK2 includes 16 unique functions selectable across 4 operating modes — loss-of-prime, pressure guard (high/low), single-point snap-action, and dual-pump control. Different functions are available in different modes; see the printed data sheet PDF below for the full mode × function matrix.

3-Phase Pumping Systems

The E30 MK2 can be used to control either single-phase or 3-phase pumps, provided a 220–240 V AC or 24 V AC supply is available at the installation site. For 3-phase motors the E30 drives an interposing contactor — use the Pump Controller Power Calculator to size the contactor and verify cable rating + voltage drop.

Open the Pump Controller Power Calculator →

Application Restriction

The E30 MK2 is an industrial control device, specifically designed for use in industrial, agricultural and mining applications. It must never be used for any other application. Installation must be carried out by a qualified pump engineer, and all electrical work by a licensed electrician.

Hazardous Areas

The E30 MK2 is not certified for use in hazardous areas and must not be installed in any area classified as hazardous under AS/NZS 60079.10 (Zone 0, 1, 2, 20, 21 or 22).

Serviceability

The E30 MK2 digital pressure switch is not user serviceable. However, spare parts are available from Kelco Engineering or from your distributor.